Nest Thermostat F10 Fix: No Power to Y1 (Cooling) Wire

What This Error Means

F10 on a Nest Thermostat means the thermostat is not seeing 24V power on the Y1 (cooling) wire when it tells the AC to turn on.

In plain English: the Nest is calling for cooling, but the air conditioner control circuit never wakes up, so you get no cold air.

Official Fix

Here’s the clean, manual-approved way to deal with F10 before you start tearing things apart.

  • Kill the power first.
    Turn off the HVAC breaker at the electrical panel and any switch next to the furnace/air handler. You do NOT want 24V live while you’re poking wires.
  • Pop the Nest off the wall.
    Grab the thermostat and pull it straight toward you to remove the display from the base.
  • Check the Y1 wire at the Nest base.
    – The wire should be in the Y1 terminal, not half hanging out.
    – You should see about 1/4 inch of bare copper, fully inserted.
    – Tug it gently. If it slips, push the button and reinsert it firmly.
  • Check the R (or Rc/Rh) wire too.
    If R is loose, Nest can’t send a proper cooling call. R should be solidly clicked into its terminal.
  • Make sure the system power switch is ON.
    At the furnace/air handler there’s often a light-switch-style power switch. It has to be ON, or the control board won’t send 24V to Y1.
  • Turn the breaker back on.
    Restore power at the panel and at the furnace/air handler switch.
  • Restart the Nest.
    Press and hold the Nest ring for about 10 seconds until it reboots, then let it start up fully.
  • Test cooling.
    On the Nest: set mode to Cool and drop the setpoint well below room temp. Wait a couple of minutes to see if the F10 clears and the outdoor unit and blower start.

If F10 comes right back after this, the official next step is: stop there and call a Nest Pro or HVAC tech. Nest’s docs basically cap you at wiring checks and power resets.

The Technician’s Trick

Here’s how a real tech separates “Nest problem” from “AC system problem” fast and tracks down what’s actually killing Y1 power.

  • Power off at the breaker. Again.
    You’re going into the air handler/furnace cabinet now. Breaker OFF.
  • Open the furnace/air handler panel.
    Remove the front cover to expose the control board and low-voltage wiring. There’s usually a door switch; keep that pressed in when testing, or tape it down briefly if you’re comfortable.
  • Look for a blown low-voltage fuse.
    Most modern boards have a small 3A or 5A automotive-style blade fuse. If it’s smoked or the metal link is broken, that’s why Y1 has no power. Replace it with the same type and rating only after you’ve checked for shorts.
  • Check for obvious shorts in the thermostat cable.
    – Any spots where the cable is crushed, chewed, or pinched in metal?
    – At the board and at the Nest base, make sure no bare copper from different wires is touching.
  • Use the jump-test to bypass the Nest.
    – With power ON at the furnace and the door switch held in, temporarily jumper R to Y (Y1) at the equipment control board using a short piece of wire.
    – If the blower and outdoor unit kick on: the HVAC side is fine. Your problem is at the thermostat or its wiring (bad Nest base, broken wire run).
    – If nothing happens: the issue is in the equipment (blown fuse, bad transformer, float switch open, or bad board).
  • Check the condensate safety/float switch.
    Many systems kill the Y1 circuit when the drain pan fills with water.
    – Look in/near the drain pan for a little switch on the drain line or pan edge.
    – If the pan is full, clear the water, flush the drain line, then reset or reseat the switch. Once that switch closes, Y1 power usually comes back.
  • Meter check (if you own a multimeter).
    – Measure between R and C at the control board: you want ~24VAC.
    – If R–C has 24V but R–Y stays dead even with a cooling call and no blown fuse, the control board may be bad.

Bottom line: if jumping R to Y makes the AC run, the Nest or the thermostat wiring is the culprit. If it doesn’t, you’re looking at a system-side repair, not a thermostat fix.

Is It Worth Fixing? (The Financial Verdict)

  • ✅ Fix: AC system under ~12 years old, issue is just a loose wire, blown low-voltage fuse, clogged condensate line, or bad Nest base; repair is usually cheap and absolutely worth doing.
  • ⚠️ Debatable: System in the 12–15 year range, repeated fuse blows or control board issues; if parts and labor start pushing a few hundred dollars, compare that to putting the money toward a new, more efficient system.
  • ❌ Replace: System 15+ years old, multiple failures (board, compressor, or fan motor) on top of this F10 issue; dropping big money into an antique usually costs more long term than replacing the whole setup.